Main characteristics

  • Primary Measurement: Automatically captures and records voltage, current, power, power factor, electrical energy and related values
  • Compatible with Fluke Connect®: View data locally on the instrument or over your organization's WiFi network using the Fluke Connect mobile app and desktop software.
  • The instrument is easily powered: Power supply to the instrument directly from the measurement circuit
  • Security Level: Incoming wires and downstream loads are rated for 600 V CAT IV/1000 V CAT III.
  • Measure all three phases: 3 flexible current probes included
  • Fully documented: More than 20 different recorded data session packages can be stored on the device. Virtually all measurements are automatically logged, so you never lose track of measurement trends. These trends can even be viewed during the logging session and before downloading for real-time analysis!
  • Optimized user interface: Quick-guide graphical setup ensures you capture the right data every time, while intelligent verification features indicate whether the connection is correct, reducing user concerns
  • Bright color touch screen: Easy field analysis and data checking on a fully graphical display.
  • Optimized user interface: Quick setup in graphical steps with instructions to get the right data every time, and intelligent validation to reduce uncertainty in device connections
  • Completion of "Field Setup" via the front panel application: No need to return to the office for downloads and setups, or to carry a computer to the electrical panel
  • Fully integrated records: Connecting other Fluke Connect devices to the Fluke 1734 allows you to simultaneously record two additional measurement parameters, virtually all of which are available on a Fluke Connect wireless digital multimeter or module*.
  • Energy Analyze Plus application software: Download and analyze the details of power consumption using the automatic reporting feature

*Not all models are available in all areas. Please consult your local Fluke representative.

SKU:Fluke 1732 Category. Brand.

Inquire about this product

Product Overview: Fluke 1732 and 1734 Handheld Three-Phase Power Meters

Which three-phase recorder is right for you?

Three-phase power meter Power Quality Recorder
functionality 1732 Handheld Three-Phase Power Meter 1734 Handheld Three-Phase Power Meter 1736 Power quality recorders 1738 Power quality recorders
Load Research - - - -
Energy consumption assessment - - - -
Neutral line current measurement (four current channels) - -
Harmonic Measurement - -
Capture voltage events - -
Advanced Analytics:
Waveform and surge event capture
PQ Health status (EN51060)
Upgrade package* -
IEEE519 Total Harmonic Distortion Measurement selectable selectable
Fully integrated with Fluke Connect® for logging Upgrade package* - Upgrade package* -
WiFi selectable - - -
Wi-Fi / Bluetooth selectable - selectable -
Magnetic Probe Kit selectable - selectable -
Magnetic Hooks selectable - selectable -
Connect via WiFi wireless router A free software license is required for product registration. A free software license is required for product registration.
*The upgrade kit can be used to upgrade an existing 1732 Handheld 3-Phase Power Meter that has the same functionality as the 1734 Handheld 3-Phase Power Meter, and can also be used to upgrade an existing 1736 Power Quality Recorder that has the same functionality as the 1738 Advanced Power Quality Recorder. Note that the 1732 and 1734 handheld three-phase wattmeters cannot be upgraded to function as the 1736 and 1738 Power Quality Loggers.
Please consult your dealer for more information on upgrade packages.

The Fluke 1732 and 1734 Handheld 3-Phase Power Meters introduce a new and simple way to help users identify the source of wasted energy consumption. Find out where energy is being consumed in your facility - all locations including incoming wires and individual circuits - and at what moment it is being consumed. Remotely accessing data and sharing it with your team through the Fluke Connect® app allows you to maintain a safer working distance and make important decisions in real time, reducing the need to use protective gear, field trips and inspections in the field.

Analyzing energy usage in your facility helps you identify energy-saving opportunities and gives you data on which to base your actions. The new Energy Analytics software package allows you to compare multiple data points over time to get a complete picture of energy use, which is the first step in reducing energy costs.

Product Specification: Fluke 1732 and 1734 Handheld Three-Phase Power Meters

Technical indicators
accurate
parameters range (of scales or measuring equipment) resolution (of a photo) Intrinsic accuracy at reference conditions (% reading + % range)
input voltage 1000 V 0.1 V ±(0.2% + 0.01%)
Current: direct input i17xx-flex 1500 12" 150 A 0.1 A ±(1% + 0.02%)
1500 A 1 A ±(1% + 0.02%)
i17xx-flex 3000 24" 300 A 1 A ±(1% + 0.03%)
3000 A 10 A ±(1% + 0.03%)
i17xx-flex 6000 36" 600 A 1 A ±(1.5% + 0.03%)
6000 A 10 A ±(1.5% + 0.03%)
i40s-EL Current Clamp 4 A 1 mA ±(0.7% + 0.02%)
40 A 10 mA ±(0.7% + 0.02%)
frequency 42.5 Hz to 69 Hz 0.01 Hz ± (0.1%)
auxiliary input ±10 VDC 0.1 mV ±(0.2% + 0.02%)
Voltage min/max 1000 V 0.1 V ±(1% + 0.1%)
Current min/max Defined by Annex Defined by Annex ±(5% + 0.2%)
Voltage THD 1000% 0.1% ±0.5
Current THD 1000% 0.1% ±0.5
Inherent Uncertainty ± (% of reading + % of range)¹
parameters magnitude of impact iFlex 1500-12 iFlex 3000-24 iFlex 6000-36 i40S-EL
150 A / 1500 A 300 A / 3000 A 600 A / 6000 A 4 A / 40 A
Active power P PF ≥ 0.99 1.2% + 0.005% 1.2% + 0.0075% 1.7% + 0.0075% 1.2% + 0.005%
Active energy Ea PF ≥ 0.99 1.2% + 0.005% 1.2% + 0.0075% 1.7% + 0.0075% 1.2% + 0.005%
Apparent power S 0 ≤ PF ≤ 1 1.2% + 0.005% 1.2% + 0.0075% 1.7% + 0.0075% 1.2% + 0.005%
Apparent energy Eap 0 ≤ PF ≤ 1 1.2% + 0.005% 1.2% + 0.0075% 1.7% + 0.0075% 1.2% + 0.005%
Reactive power Q 0 ≤ PF ≤ 1 2.5% of measured apparent power
Reactive energy Er 0 ≤ PF ≤ 1 2.5% of measured apparent power
Power factor PF - ±0.025
Displacement power factor - ±0.025
DPF/cosϕ - ±0.025
Additional uncertainty in range¹ P-N>250 V 0.015% 0.0225% 0.0225% 0.015%
¹ Range = 1000 V x current range
Reference conditions:

  • Environment:23 °C ±5 °C, instrument operated for at least 30 minutes, no external electric/magnetic fields, RH <65%
  • Input conditions:CosΦ/PF=1, sinusoidal signal f=50 Hz/60 Hz, power supply 120 V/230 V ±10%.
  • Current and power indicators:Input voltage 1 ph: 120 V/230 V or 3 ph wye/delta: 230 V/400 V Input current: I > I range of 10%
  • Clamp primary conductor or Rogowski coil in center position
  • Temperature coefficient: 0.1 times the specified accuracy per degree Celsius above 28 °C or below 18 °C
Electrical specifications
power supply
Voltage range 100 V to 500 V when supplied via the measuring circuit with a safe input plug
100 V to 240 V with standard power cord (IEC 60320 C7)
power wastage 50 VA maximum (15 VA maximum with IEC 60320 input)
energy efficiency ≥ 68.2% (energy efficiency code compliant)
Maximum no-load loss < 0.3 W (only when using IEC 60320 inputs)
Mains frequency 50/60 Hz ± 15%
batteries Lithium-ion battery 3.7 V, 9.25 Wh (customer replaceable)
Battery powered runtime 4 hours in standard operating mode, up to 5.5 hours in power saving mode
charging time < 6 hours
data acquisition
resolution (of a photo) 16-bit synchronized sampling
sampling frequency 10.24 kHz at 50/60 Hz, synchronized to power supply frequency
Input Signal Frequency 50/60 Hz (42.5 to 69 Hz)
Type of wiring method 1-φ, 1-φ IT, split-phase, 3-φ delta, 3-φ wye, 3-φ wye IT, 3-φ wye balance, 3-φ Aron/Blondel (two-meter method), 3-φ open-leg delta, current only (load analysis)
data storage Internal flash memory (not user replaceable)
Memory capacity Typical: 10 logged sessions of 8 weeks, 1 minute intervals, and 500 events¹.
¹The number of possible logging sessions and logging periods depends on the user's needs.
fundamental interval
Parameters measured Voltage, Current, Aux, Frequency, THD V, THD A, Power, Power Factor, Base Wave Power, DPF, Electrical Energy
Average interval 1 sec, 5 sec, 10 sec, 30 sec, 1 min, 5 min, 10 min, 15 min, 30 min
Average time min/max Voltage, current: full cycle updated every half week RMS Auxiliary power: 200ms
Demand interval (energy meter mode)
Parameters measured Electrical energy (Wh, varh, VAh), PF, maximum demand, cost of electrical energy
intervals 5 min, 10 min, 15 min, 20 min, 30 min, off
standards-compliant
power (output) IEEE 1459
communication interface
USB-A File transfer via USB flash drive, firmware update
Maximum current: 120 mA
WiFi File transfer and remote control via direct connection or WiFi network
bluetooth Reading Auxiliary Measurement Data from Fluke Connect® 3000 Series Modules (requires 1734 or 1732 upgrade option)
USB-mini Download data to PC
Voltage Input
input channel 4 (three-phase and zero line)
Maximum Input Voltage 1000 Vrms, CF 1.7
Input Impedance 10 MΩ
Bandwidth (-3 dB) 42.5 Hz - 3.5 kHz
resizing 1:1, variable
Voltage safety level 1000 V CAT III/600 V CAT IV
Current Input
input channel 3, automatic mode selection for connected sensors
Input Voltage Current clamp input: 500 mVrms/50 mVrms; crest factor 2.8
Rogowski Roche Coil Input 150 mVrms/15 mVrms at 50 Hz, 180 mVrms/18 mVrms at 60 Hz; crest factor 4; all within probe rated range
range (of scales or measuring equipment) Using the Fine Flex Current Probe i17XX-flex1500 12 for 1 A to 150 A/10 A to 1500 A
Using the fine flexible current probe i17XX-flex3000 24 for 3 A to 300 A/30 A to 3000 A
Using the Fine Flex Current Probe i17XX-flex6000 36 for 6 A to 600 A/60 A to 6000 A
40 mA to 4 A/0.4 A to 40 A (40 A Current Clamp i40s-EL)
Bandwidth (-3 dB) 42.5 Hz - 3.5 kHz
resizing 1:1, variable
auxiliary input
input channel ="2"
Input range 0 to ± 10 VDC, 1 reading/second
Variation factor (applicable from 2014) Format: mx + b (gain and offset) user configurable
Unit display (applicable from 2014) User configurable (7 characters, e.g. °C, psi or m/s)
wireless connection
input channel ="2"
Supported Modules Fluke Connect® 3000 Series
harvest 1 reading/second
Environmental indicators
operating temperature -10 °C to +50 °C (14 °F to 122 °F)
storage temperature -20 °C to +60 °C (-4 °F to 140 °F) including battery: -20 °C to +50 °C (-4 °F to 122 °F)
Operating humidity 10 °C to 30 °C (50 °F to 86 °F) Maximum relative humidity 95%
30 °C to 40 °C (86 °F to 104 °F) Maximum relative humidity 75%
40 °C to 50 °C (104 °F to 122 °F) Maximum relative humidity 45%
Working altitude 2000 m (down to 1000 V CAT II/600 V CAT III/300 V CAT IV up to 4000 m)
Storage altitude 12,000m
housings IP50 (in accordance with EN60529)
vibration testing MIL-T-28800E, Type 3, Class III, Type B
safety IEC 61010-1
IEC power input: overvoltage category II, pollution class 2
Voltage side: Overvoltage category IV, pollution class 2
IEC 61010-2-031: CAT IV 600 V / CAT III 1000 V
electromagnetic compatibility EN 61326-1: Industry CISPR 11: Group 1, Class A
Korea (KCC): Class A equipment (industrial broadcasting and communications equipment)
USA (FCC): 47 CFR 15 Part B. This product is considered tax-exempt equipment under Section 15.103.
temperature coefficient 0.1 x accuracy index/°C
General technical indicators
Color LCD display 4.3-inch active matrix TFT, 480 pixels x 272 pixels, resistive touch screen
warranty period Instrument and power supply: two years (excluding batteries)
Annex: One year
Calibration cycle: two years
sizes Instrument: 19.8 x 16.7 x 5.5 cm (7.8 x 6.6 x 2.2 in)
Power supply: 13.0 x 13.0 x 4.5 cm (5.1 x 5.1 x 1.8 in)
When the instrument is connected to the power supply: 19.8 x 16.7 x 9 cm (7.8 x 6.6 x 3.5 in)
weights Instrument: 1.1 kg (2.5 lb)
Power: 400 g (0.9 lb)
tamper-proof Anti-theft lock slot
i17xx-flex 1500 12 Flexible Current Probe Specifications
measuring range 1 to 150 A AC / 10 to 1500 A AC
lossless current 100 kA (50/60 Hz)
Inherent error at reference conditions* ±0.7% of reading
173x + iFlex Accuracy ± (1% of reading + 0.02% of range)
Temperature coefficients beyond the operating temperature range 0.05%/°C of reading, 0.09%/°F of reading
operating voltage 1000 V CAT III, 600 V CAT IV
Probe cable length 305 mm (12 in)
Probe Cable Diameter 7.5 mm (0.3 in)
Minimum bending radius 38 mm (1.5 in)
Output cable length 2 m (6.6 ft)
weights 115 g
Probe Cable Material TPR
Connector Material POM + ABS/PC
output cable TPR/PVC
operating temperature Tested at a wire temperature of -20 °C to +70 °C (-4 °F to 158 °F), not exceeding 80 °C (176 °F)
Non-operating temperature -40 °C to +80 °C (-40 °F to 176 °F)
Relative humidity in working condition 15% to 85% Non-Condensing
IP rating IEC 60529:IP50
warranty period 1 year
* Reference conditions:

  • Ambient: 23 °C ± 5 °C, no external electric/magnetic fields, RH 65%
  • Primary side conductor at center