:: Compliance with SPECpower(R) standards
● (R) SPECpower is a registered trademark of Standard Performance Evaluation, Inc.
Equipped with 3 test modes: AC, DC, AC+DC.
● Equipped with current accumulation/active power accumulation function
● Basic accuracy ±0.2%
:: Wide-range accuracy guarantee
Basic parameters
| Number of measuring lines | Single-phase 2-wire |
|---|---|
| Measurement items | Voltage, Current, Active Power, Apparent Power, Power Factor, Frequency, Cumulative (Current, Active Power), Waveform Peak (Voltage/Current) |
| measuring range | Voltage:AC/DC 15.000/30.00/150.00/300.0V Current:AC/DC 100.00/300.0 mA, 1.0000/3.000/10.000/30.00A Power:1.5000 W to 9.000 kW (depending on the combination of voltage and current ranges) |
| Cumulative measurement (Accrual: up to 10,000 hours) |
[Current] 6-digit display (0.00000mAh~, different polarity and sum value) [Active power]6-digit display (0.00000mWh~, different polarity and total value) |
| Input resistance (50/60 Hz) | Voltage: 2.4MΩ, Current: 10mΩ or less (direct input) |
| Basic precision | ±0.1%rdg. ±0.2%f.s. (DC), ±0.1%rdg. ±0.1%f.s. (45Hz to 66Hz) |
| Display update rate | 5 times/second |
| frequency characteristic | DC, 45Hz to 5kHz |
| waveform output | 3ch (can output voltage-current-active power instantaneous waveforms simultaneously), 1V f.s. |
| D/A output | 4ch (with simultaneous +1ch selection of voltage-current-active power), DC ±2V f.s. |
| Other Functions | [Rectification mode switching] AC+DC (Effective value), DC (Simple average), AC (Effective value), Waveform peak test function, VT-CT ratio setting, Average value function, etc. |
| connector | RS-232C interface standard, GP-IB (please select 3334-01) |
| power supply (of an appliance etc) | 100V~240V AC, 50/60Hz, up to 20VA |
| Volume and weight | 210W×100H×245Dmm, 2.5kg |
| attachment (email) | Power cord × 1, instruction manual × 1 |