PT-710 AC/DC Current Probe (0.05-100A, 100kHz)
PT-710 AC/DC Current Probe (0.05-100A, 100kHz)
PT-710 AC/DC Current Probe (0.05-100A, 100kHz)
PT-710 AC/DC Current Probe (0.05-100A, 100kHz)

PT-710 AC/DC Current Probe (0.05-100A, 100kHz)

PT-710(100kHz, 0.05-100A) AC/DC Current Probe Abbreviated Description: 100kHZ, 0.05A-10A, 10A-100A Compatible with any brand of oscilloscope.

SKU:PT-710 Categories. , Brand.

Inquire about this product

PT-710 AC/DC Current Probe (0.05-100A, 100kHz)

model number PT-710
range (of scales or measuring equipment) 100 m V/ A 10 m V/ A
Current range 0 . 05 A- 10 A peak 10 A- 100 A peak
direct current 100 A
RMS 70 A
Output Signal Percentage Error 2 %
Frequency range (- 3 d B) DC- 100 k Hz
phase shift DC- 65 Hz: < 1 . 5 ° DC- 65 Hz: < 1 °
Load Impedance ≥1 MΩ and ≤100 p F
Insertion Impedance 0 . 01 Ω
noises 6 m V 600μV
Rise/fall time 3 . 5μs
operating voltage 600 Vrms max.
common-mode voltage (electronics) 600 Vrms max.
batteries 9 V alkaline battery (NEDA 1604 A, IEC 6 LR 61 ) / standby 144 hours
Low Battery Indication When > 6.5 V, the LED is green. 5 V, the LED is green, the green light flashes and the battery needs to be replaced.
Overload indication The red LED indicates that the measured current is too high and that the measuring range needs to be changed.
Mechanical indicators
operating temperature 0 ~+ 50 °C
temperature effect Per 10 °C, < 0 . 2 %
Operating humidity 20 - 75 % RH
Maximum insertion Diameter 11 mm
exports 2 m coaxial cable terminated with insulated BNC socket
weights 330 g (with battery)
sizes 231 * 36 * 67 mm

Manual measurement, there is an error of ± 2mm

PT-710 Dimensional Drawing.jpg

45659f2f6e68b6c3e3cb59285d521741.png

Battery.jpg

Expand More
PT-710 AC/DC Current Probe (0.05-100A, 100kHz)PT-710 AC/DC Current Probe (0.05-100A, 100kHz)

Click to enquire

Product consultation and purchase:18218718851

I already understand