:: Supports the 4-electrode method with a wide range of measurement functions.
● MEC function allows measurements without disconnecting the grounding pole
● Dust and waterproof IP67, operating temperature -25°C ~ 65°C, drop proof
● The use of grounding grid assemblies eliminates the need to insert auxiliary grounding rods.
:: Reduced operating time, with a measurement time of only 6 seconds and easy setup and stowage of the test line
● Current clamps can be easily clamped whether in confined areas or measuring busbars (option)
● Supports wireless communication for transmitting measurements to a smartphone or tablet PC (when option Z3210 is installed)
:: Clamp sensors can be used for measurements (FT6041-91 set with 2 clamp sensors)
Basic parameters (accuracy guaranteed for 1 year)
※1: -25°C to 40°C (80% RH or less), 40°C to 45°C (60% RH or less), 45°C to 50°C (50% RH or less), 50°C to 55°C (40% RH or less), 55°C to 60°C (30% RH or less), 60°C to 65°C (25% RH or less). 25% RH or less)
※2: With 4 rechargeable NiMH batteries (23°C reference value)
| Measurement items | Ground resistance measurement (4-electrode method, 3-electrode method, 2-electrode method, MEC function, clamp type), Low resistance measurement (4-terminal method, 2-terminal method), Voltage to ground measurement, earth resistivity |
|---|---|
| Voltage measurement to ground | 0 to 30.0 Vrms, Accuracy: ±2.3% rdg ±8 dgt (50/60 Hz), ±1.3% rdg ±4 dgt (DC) |
| functionality | Charged warning display, automatic power saving, earth resistivity display (4-electrode method only), zero setting, auto hold, continuous measurement, wireless communication (when Z3210 is installed), buzzer, comparator, display switching, overvoltage to earth display (low resistance measurement) |
| Temperature range | -25°C to 65°C, *1 (non-condensing) |
| Storage temperature and humidity range | -25°C to 65°C, below 80% RH (non-condensing) |
| Dustproof, Waterproof | IP65, IP67 (IEC 60529, EN 60529) |
| Applicable standards | EN IEC 61010-2-030: 2021 (safety), EN 61326 (EMC), EN 61557-1,EN 61557-10, EN 61557-4 (low resistance), EN 61557-5 (earth resistivity meter) |
| power supply | Ni-MH rechargeable batteries size 5 × 4 or Alkaline batteries size 5 (LR6) × 4 |
| Number of measurements
(*2) |
500 cycles (3-electrode method, Z3210 not installed), 400 cycles (3-electrode method, Z3210 installed, wireless communication) |
| Volume and weight | Approx. 189W × 148H × 48D mm, approx. 765 g (including battery and case) |
| attachment (email) | Auxiliary grounding rod L9840 (1 set of 2) × 2, Test lead L9841 × 1, Test lead L9845-31 × 1, Test lead L9845-33 × 1, Test lead L9845-52 × 1, Grounding mesh assembly L9846 × 2, Test lead L9787 × 1, Carrying case C0208 × 1, Carrying case C0209 × 1, Alkaline battery No. 5 (LR6) × 1 4, Instruction manual ×1 |
Ground resistance measurement (4-electrode method, 3-electrode method, 2-electrode method)
| operating method | Applied Voltage, Voltage and Current Measurement (Effective Resistance Measurement by Synchronous Detection) | |||||
|---|---|---|---|---|---|---|
| Measurement range | 3 Ω (0 to 3.000 Ω) | 30 Ω (0 to 30.00 Ω) | 300 Ω (30.0 Ω to 300.0 Ω) | 300 Ω or more 3 k Ω or less (300 Ω to 3000 Ω) | 3 k Ω or more 30 k Ω or less (3.00 k Ω to 30.00 k Ω) | 30 k Ω or more 300 k Ω or less (30.0 k Ω to 300.0 k Ω) |
| accurate | unspecified | ±1.5% rdg ±6 dg | ±1.5% rdg ±4 dgt | |||
| Permissible resistance of auxiliary earth electrode | 5 kΩ | 50 kΩ | 100 kΩ | |||
| Allowable voltage to ground | 30 V rms or 42.4 V peak | |||||
MEC function (4-electrode method + clamp meter, 3-electrode method + clamp meter)
| Measurement method | Applied Voltage, Voltage and Current Measurement (Effective Resistance Measurement by Synchronized Detection) | |||
|---|---|---|---|---|
| Measurement range | 30 Ω (0.00 Ω to 30.00 Ω) | 300 Ω (30.0 Ω to 300.0 Ω) | 3000 Ω (300 Ω to 3000 Ω) | 30.00 k Ω (3 k Ω ~ 30.00 k Ω) |
| accurate | ±5% rdg ±6 dgt | ±5% rdg ±3 dgt | ||
Ground resistance measurement (clamp type)
| Measurement method | Applied Voltage, Voltage and Current Measurement (Effective Resistance Measurement by Synchronized Detection) | ||
|---|---|---|---|
| Measurement range | 20 Ω (0.02 Ω to 20.00 Ω) | 200 Ω (20.0 Ω to 200.0 Ω) | 500 Ω (200 Ω to 500 Ω) |
| accurate | ±7% rdg ±3 dgt | ±35% rdg | |
Low Resistance Measurement
| open circuit voltage | 4.0 V to 6.9 V | ||
|---|---|---|---|
| measured current | 200 mA or more | ||
| Measurement range | 30 Ω (0.00 Ω to 30.00 Ω) | 300 Ω (30.0 Ω to 300.0 Ω) | 3000 Ω (300 Ω to 3000 Ω) |
| accurate | ±3 dgt (0.00 Ω ~ 0.19 Ω) ±2% rdg ±2 dgt (0.20 Ω ~ 10.00 Ω) | ±2% rdg ±2 dgt | |
Comprehensive test and measurement service provider-Shenzhen Weike Electronic Technology Co.