-Displays 4 parameters simultaneously
-Power meter that can measure 5W and 60mA; can measure from 5W up to 360kW with a low current of 60mA.
-In addition to current, voltage and power, it is also possible to measure simple cumulative power and phase sequence.
-Operating system that supports fast measurements
-Transfers measurements to a smartphone by holding the data and quickly records the data
-GENNECT Cross can analyze high harmonics from the 1st to the 30th (when wireless adapter Z3210 is installed)
Product Feature Name
CAT IV 600, CATIII 1000V
Basic parameters (accuracy guaranteed for 1 year, adjusted accuracy guaranteed for 1 year)
※1) Phase angle obtained from the zero crossing of current and voltage
(*2) Harmonics can be displayed using the application software (GENNECT Cross).
Measuring Lines | Single-phase, three-phase (balanced, no waveform distortion) |
---|---|
Measurement items | Voltage, current, peak voltage/current waveform, active/apparent/reactive power, power factor, phase angle*1, frequency, simple single-phase energy [When Z3210 is installed*2] Voltage/current harmonics |
Voltage range | [Measurement range] 80.0 V to 600.0 V, single range, basic accuracy 45-66 Hz:±0.7%rdg. ±3 dgt., (Frequency characteristics: 45-1 kHz, true RMS) |
Current range | [Measuring range] 0.060-600.0 A, 3 ranges, basic accuracy 45-66 Hz: ±1.3%rdg. ±3dgt., (frequency characteristics: 45-1 kHz, true RMS) |
power range | [Single-phase] 0.005 kW to 360.0 kW Basic accuracy: ±2.0% rdg. ±7 dgt. (50/60 Hz power factor = 1) [Balanced 3-phase 3-wire] 0.020 kW ~ 623.5 kW Basic accuracy: ±3.0% rdg. ±10 dgt. (50/60 Hz power factor = 1) [Balanced 3-phase 4-wire] 0.040 kW ~ 1080 kW Basic accuracy: ±2.0% rdg. ±3 dgt. (50/60 Hz power factor = 1) |
harmonic (wave with frequency an integer multiple of the fundamental) | [When installing Z3210 installation※2] 30th harmonic level/containing rate/total harmonic distortion rate of voltage and current |
Other Functions | [Phase Angle*1] Superiority -180.0°~ Delay 179.9° [Power factor] -1.000 to 1.000 [Harmonics] 45.0Hz to 999.9Hz Peak, phase check, max/min/average display, auto hold, meter comparison, unbalanced three-phase power projection display, etc. |
Dust and water resistance | IP20 (voltage measurement in completely dry condition, with jaws closed) IP54 (when stored) |
power supply | Alkaline Battery No. 7 (LR03) × 2 Continuous use time: approx. 25 hours (without Z3210 installed), approx. 18 hours (with Z3210 installed and wireless communication) Other conditions:AC 100 A measurement, backlight off, 23°C reference value |
Measurable conductor diameter | φ46 mm, Jaw size: 92 W × 18 D mm |
Volume and weight | 65W × 241H × 35D mm, 450 g |
attachment (email) | Connecting cable L9257×1, Alkaline battery No. 7 (LR03) ×2, Carrying case C0203×1, Instruction manual ×2, Precautions for use ×1 |
Wireless-capable countries (CM3286-01) Updated: 2021/10/8
wireless authentication | Austria, Bangladesh, Belgium, Brazil, Bulgaria, Canada, Chile, China, Colombia, Croatia, Cyprus, Czech Republic, Denmark, Estonia, Finland, France, Georgia, Germany, Greece, Hong Kong, Hungary, Iceland, India, Indonesia, Ireland, Israel, Italy, Japan, Kenya, Korea, Latvia, Liechtenstein, Lithuania, Luxembourg, Macao, Malta, Myanmar, Netherlands, Norway, Peru, Philippines, Poland, Portugal, Romania, Serbia, Singapore, Slovakia, Slovenia, Spain, Sweden, Switzerland, Thailand, Turkey, United Kingdom, United States, Viet Nam. |
---|